V-TAC on-grid inverter SKU 11631 , manufactured by INVT with code XG60KTR , three-phase 60 KW. Number of strings for MPPT 3/3/3/3 is a device that converts the direct current supplied by the solar panels into alternating current with three-phase output for the consumption of commercial premises or industries.
Compliant with CEI-021 standard
It is possible to control consumption remotely via the Apps:
- SOLARMAN Smart (Download: iOS / Android / Web App ), for private and domestic use;
- SOLARMAN Business (Download: iOS / Android / Web App ), for Corporate Use, with the possibility of having a centralized view of all the systems built and issuing the authorizations for accessing the system to the end user.
To add a new system, follow the initialisation procedure of the Datalogger (WiFi module) indicated in the instruction manual.
Specification
XG60KTR
Input (DC)
Max. Input Power
96kW
Max. Input Voltage
1100V
Start Voltage
250V
Rated Input Voltage
600V
Full-load MPP Voltage Range
520V ~ 850V
MPPT Voltage Range
200V ~ 1000V
Number of MPP Trackers
4
Number of string per MPPT
3 / 3 / 3 / 3
Max. Current per MPPT
39A
Max. Short Circuit Current per MPPT
48A
Output (AC)
Max. Output Current
95.6
Rated Output Power
60kW
Max. Output Power
66VA
Rated Grid Frequency
50Hz / 60Hz
Rated Grid Voltage
230Vac / 400Vac
Power Factor
>0.99 (0.8 leading~0.8 lagging)
THDi
<3% (Rated Power)
Efficiency
Max. Efficiency
98.80%
European Efficiency
98.40%
MPPT Efficiency
99.90%
Protection
DC reverse polarity protection
Yes
Anti-islanding protection
Yes
AC short circuit protection
Yes
Residual current monitoring unit
Yes
Insulation resistance monitoring
Yes
Ground fault monitoring
Yes
Grid monitoring
Yes
PV string monitoring
Yes
Surge protection
Type II
AFCI protection
Optional
Communication
Display
LED / LCD / WiFi+App
Communication
Standard:RS485/ USB Optional:WiFi / GPRS / Ethernet
Standard Compliance
Grid Connection Standards
IEC 61727, IEC 62116, IEC 60068, IEC 61683, VDE-AR-N 4110:2018, VDE-AR-N 4105:2018,VDE-AR-N 4120:2018, EN 50549, AS/NZS 4777.2:2020, CEI 0-21, VDE 0126-1-1/A1 VFR 2014,UTE C15-712-1:2013, DEWA DRRG, NRS 097-2-1, MEA/PEA, C10/11, G98/G99
Safety / EMC
IEC 62109-1:2010, IEC 62109-2:2011, EN 61000-6-2:2005, EN 61000-6-3:2007/A1:2011
General Data
Dimensions (W x H x D)
650 x 450 x 260 mm
Weight
50kg
Operating Temperature Range
-30°C ~ +60°C
Cooling Method
Smart Cooling
Protection Degree
IP66
Max. Operating Altitude
4000m
Relative Humidity
0 ~ 100%
Topology
Transformerless
Night Power Consumption
<1W