Energy cables for interiors and wiring, flexible single core insulated in S17 quality PVC, fire retardant and with low emission of corrosive gases and zero halogens. Resistant to mechanical stress, fire and flame retardant, very low emission of halogens, fumes, toxic and corrosive gases. Good behavior at low temperatures, good flexibility, smoothness and excellent peelability. Good abrasion resistance. Compliant with the regulation in accordance with the European Construction Products Regulation CPR (EU) n.305/11.
Applications
Single-core cables suitable for installation in visible or built-in pipes, even in places with a fire hazard, in similar closed systems and in any case only inside buildings. Also used for fixed installation of switching and command equipment and inside lighting equipment. Not suitable for outdoor installation.
- Model: 200GR6
- Section - Nominal n° x mm²: 1 x 6
- Diameter - Indicative conductor (mm): 3
- Average insulation thickness (mm): 0.8
- Maximum external diameter (mm): 6.3
- Indicative weight Kg./Km. : 63
- Electrical resistance at 20° C. - Maximum Ω/Km: 3.3
- Conductor: Class 5 flexible round wire annealed red copper
- Core insulation: Polyvinyl chloride (PVC) S17 quality
- Marking: Stamping on the insulation every 1 m
- Rated voltage: Uo/U: 450/750V
- Maximum working temperature: 70°C
- Minimum operating temperature: -10°C
- Maximum short circuit temperature: 160°C
- Minimum laying temperature: 5°C
- Minimum recommended bending radius: 4 times the diameter of the cable
- Maximum recommended traction force: 50 N/mm² of section
- Color: Grey.
- skein 100 meters.
Compliant with the construction products regulation (CPR)
- Standard : EN 50575:2014+A1:2016
- Class: Cca-s3, d1, a3
- Classification (CEI UNEL 35016): EN 13501-6
- Heat and smoke emission during flame development: EN 50399
- Vertical flame propagation: EN 60332-1-2
- Corrosive gases and halogens: EN 60754-2
Reference standards
- CEI UNEL 35716
- CEI EN 60332-1-2
- 2014/95/EU
- 2014/35/EU
- 2011/65/EU